Monday, 2 January 2012

Electrical installation design methodology


For the best results in electrical installation design it is recommended to read all the chapters of this guide in the order in which they are presented.

Contents

  •  Listing of power demands
  •  Service connection
  •  Electrical Distribution architecture
  •  Protection against electric shocks
  •  Circuits and switchgear
  •  Protection against overvoltages
  •  Energy efficiency in electrical distribution
  •  Reactive energy
  •  Harmonics
  •  Particular supply sources and loads
  • A green and economical energy
  •  Generic applications
  •  EMC Guidelines

Listing of power demands

The study of a proposed electrical installation requires an adequate understanding of all governing rules and regulations. The total power demand can be calculated from the data relative to the location and power of each load, together with the knowledge of the operating modes (steady state demand, starting conditions, non simultaneous operation, etc.)
From these data, the power required from the supply source and (where appropriate) the number of sources necessary for an adequate supply to the installation are readily obtained.
Local information regarding tariff structures is also required to allow the best choice of connection arrangement to the power-supply network, e.g. at medium voltage or low voltage level.

Service connection

This connection can be made at:
  • Medium Voltage level
    A consumer-type substation will then have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at medium-voltage or low-voltage is possible in this case.
  • Low Voltage level
    The installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs.

Electrical Distribution architecture

The whole installation distribution network is studied as a complete system. A selection guide is proposed for determination of the most suitable architecture. MV/LV main distribution and LV power distribution levels are covered.
Neutral earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the type of loads.
The distribution equipment (panelboards, switchgears, circuit connections, ...) are determined from building plans and from the location and grouping of loads. The type of premises and allocation can influence their immunity to external disturbances.

Protection against electric shocks

The earthing system (TT, IT or TN) having been previously determined, then the appropriate protective devices must be implemented in order to achieve protection against hazards of direct or indirect contact.

Circuits and switchgear

Each circuit is then studied in detail. From the rated currents of the loads, the level of short-circuit current, and the type of protective device, the cross-sectional area of circuit conductors can be determined, taking into account the nature of the cableways and their influence on the current rating of conductors.
Before adopting the conductor size indicated above, the following requirements must be satisfied:
  • The voltage drop complies with the relevant standard
  • Motor starting is satisfactory
  • Protection against electric shock is assured
The short-circuit current Isc is then determined, and the thermal and electrodynamic withstand capability of the circuit is checked.
These calculations may indicate that it is necessary to use a conductor size larger than the size originally chosen.
The performance required by the switchgear will determine its type and characteristics.
The use of cascading techniques and the discriminative operation of fuses and tripping of circuit breakers are examined.

Protection against overvoltages

Direct or indirect lightning strokes can damage electrical equipment at a distance of several kilometers. Operating voltage surges, transient and industrial frequency over-voltage can also produce the same consequences.The effects are examined and solutions are proposed.

Energy efficiency in electrical distribution

Implementation of measuring devices with an adequate communication system within the electrical installation can produce high benefits for the user or owner: reduced power consumption, reduced cost of energy, better use of electrical equipment.

Reactive energy

The power factor correction within electrical installations is carried out locally, globally or as a combination of both methods.

Harmonics

Harmonics in the network affect the quality of energy and are at the origin of many disturbances as overloads, vibrations, ageing of equipment, trouble of sensitive equipment, of local area networks, telephone networks. This chapter deals with the origins and the effects of harmonics and explain how to measure them and present the solutions.

Particular supply sources and loads

Particular items or equipment are studied:
  • Specific sources such as alternators or inverters
  • Specific loads with special characteristics, such as induction motors, lighting circuits or LV/LV transformers
  • Specific systems, such as direct-current networks

A green and economical energy

The solar energy development has to respect specific installation rules.

Generic applications

Certain premises and locations are subject to particularly strict regulations: the most common example being residential dwellings.

EMC Guidelines

Some basic rules must be followed in order to ensure Electromagnetic Compatibility. Non observance of these rules may have serious consequences in the operation of the electrical installation: disturbance of communication systems, nuisance tripping of protection devices, and even destruction of sensitive devices.

Ecodial software

Ecodial software provides a complete design package for LV installations, in accordance with IEC standards and recommendations.

The following features are included:
  • Construction of one-line diagrams
  • Calculation of short-circuit currents
  • Calculation of voltage drops
  • Optimization of cable sizes
  • Required ratings of switchgear and fusegear
  • Discrimination of protective devices
  • Recommendations for cascading schemes
  • Verification of the protection of people
  • Comprehensive print-out of the foregoing calculated design data



The link is which is given below


The Following link will helps you to estimate the required load




After completion of the load estimation then we have to calculate the total connected load of that required building. If it is an apartment then calculate the connected load of the each flat and then calculate the connected load of the total construction.

For the  load calculation we need to know the below formulae:


Convert Watts to Volts: 
               Voltage = Watts / AMPS 
                  E = P ÷ I 
Convert Watts to AMPS: 
              AMPS = Watts / Voltage 
                I = P ÷ E 
Example: 
2,300 WATTS = 2300W divided by 120v = 19.1 AMPS 

(for 3 Phase divide by 1.73) 
Convert AMPS to Watts:
             Watts = Voltage x Amps 
              P = E x I 
Example: 
19.1 AMPS multiplied by 120v = 2300 Watts 
(for 3 phase multiply by 1.73) 


Convert Horse Power to AMPS: 

            HORSEPOWER= (V x A x EFF)÷746 
            EFFICIENCY= (746 x HP)÷(V x A) 

Multiply Horse Power by 746w (1 HP = 746 Watts) 
Find Circuit Voltage and Phase 

Example: 
30 HP at 480 (3 Phase) - 746 multiplied by 30 = 22380 
22380 divided by 480 (3 Phase) = 46.5 
46.5 divided by 1.73 = 29.5AMPS 
Multiply all the motor loads by 1.50% and go to the next circuit size. 

Convert KVA to AMPS: 
                  Multiply KVA by 1000/voltage 

Example: 
30 KVA multiplied by 1000v = 30,000 Watts 
30,000 Watts divided by 480 = 62.5 AMPS 
(for 3 phase divide by 1.73) 

Convert KW to AMPS: 
               Multiply KW by 1000/voltage and then by power factor 
Example: 
30KW multiplied by 1000v = 30,000 
30,000 divided by 480 = 62.5 x .90 = 56.25amps 
(for 3 phase divide by 1.73) 

Symbolic:

E =VOLTS or (V = VOLTS)
P =WATTS or (W = WATTS)
R = OHMS or (R = RESISTANCE)
I =AMPERES or (A = AMPERES)
HP = HORSEPOWER
PF = POWER FACTOR
kW = KILOWATTS
kWh = KILOWATT HOUR
VA = VOLT-AMPERES
kVA = KILOVOLT-AMPERES
C = CAPACITANCE
EFF = EFFICIENCY (expressed as a decimal)

How to Convert KVA to KW
Power can be measured in kVA or kW. Power ratings on appliances can be expressed in either, but there is an important difference between the two. kVA is referred to as "apparent power," and kW as "real power." The two are equal when voltage and current are in phase, but when they are out of phase, as is often the case with alternating current, apparent power can be higher than the actual amount of real power available.


Background:
It is often necessary to turn voltage, amperage and electrical "nameplate" values from computer, network and telecom equipment into kW, KVA and BTU information that can be used to calculate overall power and HVAC loads for IT spaces.  The following describes how to take basic electrical values and convert them into other types of electrical values.  
  • The informational nameplates on most pieces of computer or network equipment usually display electrical values.  These values can be expressed in volts, amperes, kilovolt-amperes, watts or some combination of the foregoing.  

  • If you are using equipment nameplate information to develop a power and cooling profile for architects and engineers, the total power and cooling values will exceed the actual output of the equipment.  Reason:  the nameplate value is designed to ensure that the equipment will energize and run safely.  Manufacturers build in a "safety factor" when developing their nameplate data.  Some nameplates display information that is higher than the equipment will ever need - often up to 20% higher.  The result is that, in total, your profile will "over engineer" the power and cooling equipment.  Electrical and mechanical engineers may challenge your figures citing that nameplates require more power than necessary.  

  • Our advice:  Develop the power and cooling profile using the nameplate information and the formulas below and use the resultant documentation as your baseline. 

  •  Reasons:
  •  (1) It's the best information available without doing extensive electrical tests on each piece of equipment.  Besides, for most projects, you are being asked to predict equipment requirements 3-5 years out when much of the equipment you will need hasn't been invented yet. 
     
  •  (2) The engineers will not duplicate your work; they do not know what goes into a data centre.  They will only challenge the findings if they appear to be to high.  If the engineers want to challenge your figures, it's OK but have them do it in writing and let them take full responsibility for any modifications.  If you must lower your estimates, do so.  But, document everything.  There will come a day in 3-5 years when you will need every amp of power you predicted.  We've had projects where it was very evident within six months that what we predicted would come true - sometimes even earlier than we estimated.  

  • If you are designing a very high-density server room where you will have racks and racks (or cabinets and cabinets) of 1U and 2U servers tightly packed, you need to read our article entitled "IT Pros - Don't be Left in the Dust on IT Server Room Design".  

To Find Watts:
1.     When Volts and Amperes are Known
        POWER (WATTS) = VOLTS x AMPERES

We have a small server with a nameplate shows 2.5 amps.  Given a normal 120 Volt, 60 hz power source and the ampere reading from equipment, make the following calculation:  
        POWER (WATTS) = 120 * 2.5                   ANSWER:  300 WATTS

To Find Volt-Amperes (VA):

   Same as above.  VOLT-AMPERES (VA) = VOLTS x AMPERES    ANS:  300 VA

To Find kilovolt-Amperes (kVA)

1.     SINGLE PHASE

        KILOVOLT-AMPERES (kVA) = (VOLTS x AMPERES)/1000
                                                            
        Using the previous example:  120 * 2.5 = 300 VA       300 VA / 1000 = .3 kVA

2.     208-240 SINGLE-PHASE (2-POLE SINGLE-PHASE)
Given:  
We have a Sun server with an amp rating of 4.7 and requiring a 208-240 power source.  We'll use 220 volts for our calculations.
        KILOVOLT-AMPERES (kVA) = (VOLTS x AMPERES)/ 1000
        220 x 4.7 = 1034          1034 / 1000 = 1.034 kVA

3.     THREE-PHASE
Given:  
We have a large EMC Symmetrix 3930-18/-36 storage system with 192 physical volumes.  EMC's website shows a requirement for a 50-amp 208 VAC receptacle.  For this calculation, we will use 21 amps. Do not calculate any value for the plug or receptacle. 
        KILOVOLT-AMPERES (kVA) = (VOLTS x AMPERES x 1.73)/1000
               208 x 21 x 1.73 = 7,556.64          7,556.64 / 1000 =  7.556 kVA

To Find Kilowatts
Finding Kilowatts is a bit more complicated in that the formula includes a value for the "power factor".  The power factor is a nebulous but required value that is different for each electrical device.  It involves the efficiency in the use of of the electricity supplied to the system.  This factor can vary widely from 60% to 95% and is never published on the equipment nameplate and further, is not often supplied with product information.  For purposes of these calculations, we use a power factor of .85.  This arbitrary number places a slight inaccuracy into the numbers.  Its OK and it gets us very close for the work we need to do.  

1.     SINGLE PHASE
        Given:  
We have a medium-sized Compaq server that draws 6.0 amps.  
        KILOWATT (kW) = VOLTS x AMPERES x POWER FACTOR
                                                                             1000
        120 * 6.0 = 720 VA       720 VA * .85 = 612      612 / 1000 = .612 kW

2.     TWO-PHASE
Given:  
We have a Sun server with an amp rating of 4.7 and requiring a 208-240 power source.  We'll use 220 volts for our calculations.
        KILOWATT (kW) = VOLTS x AMPERES x POWER FACTOR x 2
                                                                                  1000
        220 x 4.7 x 2 = 2068          2068 x .85 = 1757.8      1757.8 / 1000 = 1.76 kW

3.     THREE-PHASE
Given:  
We have a large EMC Symmetrix 3930-18/-36 storage system with 192 physical volumes.  EMC's website shows a requirement for a 50-amp 208 VAC receptacle.  For this calculation, we will use 22 amps. Do not calculate the value of the plug or receptacle.  Use the value on nameplate.  

        KILOWATT (kW) = VOLTS x AMPERES x POWER FACTOR x 1.73
                                                                                  1000
        208x22x1.73 = 7,916.48    7,916.48 * .85 = 6,729.008    6,729.008/1000=6.729 kW

To Convert Between kW and KVA:

The only difference between kW and kVA is the power factor.  Once again, the power factor, unless known, is an approximation.  For purposes of our calculations, we use a power factor of .85.  The kVA value is always higher than the value for kW.  
        kW to kVA         kW / .85 = SAME VALUE EXPRESSED IN kVA
        kVA TO kW       kVA * .85 = SAME VALUE EXPRESSED IN kW

To Find BTUs From Electrical Values:

Known and Given:   1 kW = 3413 BTUs (or 3.413 kBTUs)
The above is a generally known value for converting electrical values to BTUs.  Many manufacturers publish kW, kVA and BTU in their equipment specifications.  Often, dividing the BTU value by 3413 does not equal their published kW value.  So much for knowns and givens.  Where the information is provided by the manufacturer, use it.  Where it is not, use the above formula. 

1) Power factor:
 In ac electrical systems, the current and voltage may not be exactly in phase. The product of voltage x current x cos(phase angle) is power. However, the portion of current that is not in phase still costs the electric company money to transmit. So they may base their rates on kVA, not on kW for commercial contracts, in essence, charging you as though the current was in-phase and represented power. (The user can install components that improve the power factor to minimize cost, and this is his incentive to do so.) When the power factor is one, kVA and kW are the same thing.

2) Time:
 kWh is the product of power and time. It is 1 kW for an hour, use it for two hours and it will be 2 kWh

It won't be a perfect estimate, but you can assume the power factor is 1, so 20 kVA = 20 kW and multiply by the hours run to get kWh.

The RMS current I in amps is equal to 1000 times the apparent power(KVA) S in kilovolt-amps, divided by the RMS voltage V in volts:
I = 1000 × S / V
So amps are equal to 1000 times kilovolt amps divided by volts.
amps = 1000 × kVA / volts
Or
A = 1000 • kVA / V

Example:
Question: 
What is the current in amps when the apparent power is 3 kVA and the voltage supply is 110 volts?
Solution:
I = 1000 × 3kVA / 110V = 27.27A
3 phase kVA to amps conversion
The RMS current I in amps is equal to 1000 times the apparent power S in kilovolt-amps, divided by the square root of 3 times the RMS voltage V in volts:
I = 1000 × S / (√3 × V )
So amps are equal to 1000 times kilovolt amps divided by the square root of 3 times volts.
amps = 1000 × kVA / (√3 × volts)
Or
A = 1000 • kVA / (√3 × V)

Example:
Question: 
What is the current in amps when the apparent power is 3 kVA and the voltage supply is 110 volts?
Solution:
I = 1000 × 3kVA / (√3 × 110V) = 15.746A

Single phase amps to kVA conversion:

The apparent power S in kilovolt-amps is equal to RMS current I in amps, times the RMS voltage V in volts, divided by 1000:
S = I × V / 1000
So kilovolt amps are equal to amps times volts divided by 1000.
kilovolt-amps = amps × volts / 1000
Or
kVA = A • V / 1000

Example:
Question: 
What is the apparent power in kVA when the current is 12A and the voltage supply is 110V?
Solution:
S = 12A × 110V / 1000 = 1.32kVA
3 phase amps to kVA conversion
The apparent power S in kilovolt-amps is equal to RMS current I in amps, times the RMS voltage V in volts, divided by 1000:
S = √3 × I × V / 1000
So kilovolt amps are equal to amps times volts divided by 1000.
kilovolt-amps = √3 × amps × volts / 1000
Or
kVA = √3 × A • V / 1000

Example:
Question:
 What is the apparent power in kVA when the current is 12A and the voltage supply is 110V?
Solution:
S = √3 × 12A × 110V / 1000 = 2.286kVA


Standard Prefixes:

Prefix used in code Prefix for written unit Multiplier:

Standard Prefixes

Prefix used in code
Prefix for written unit
Multiplier
da-
deka-
10
h-
hecto-
100
k-
kilo-
1000
M-
mega-
1e6
G-
giga-
1e9
T-
tera-
1e12
P-
peta-
1e15
E-
exa-
1e18
Z-
zeta-
1e21
Y-
yotta-
1e24
d-
deci-
1e-1
c-
centi-
1e-2
m-
milli-
1e-3
mu-
micro-
1e-6
n-
nano-
1e-9
p-
pico-
1e-12
f-
femto-
1e-15
a-
atto-
1e-18
z-
zepto-
1e-21
y-
yocto-
1e-24



Standard Units

Unit
Symbol
Definition
Comments
Time
second
sec
1 s

minute
min
60 s

hour
hr
60 min

hour
hour
1 hr
alternate symbol
hour
h
1 hr
alternate symbol
day
day
24 hr

shake
shake
10 ns

Hertz
Hz
1 s^-1







Length or Distance
international foot
ft
0.3048 m

inch
in
1.0/12.0 ft

international mile
mile
5280.0 ft

international mile
mi
1 mile
alternate symbol
milli-inch
mil
0.001 in

Parsec
pc
3.085678e16 m

League
league
3 mile

Astronomical Unit
ua
1.49598e11 m

Astronomical Unit
AU
1.49598e11 m
alternate symbol
yard
yd
3 ft

Angstrom
Ang
1e-10 m

Angstrom
\\AA
1 Ang
alternate symbol
furlong
furlong
220 yd

fathom
fathom
6 ft

Rod
rd
16.5 ft

U.S. survey foot
sft
(1200./3937.) m

U.S. survey mile
smi
5280 sft
also called statue mile
point
pt
1./72. in
Typeface Point
pica
pica
1./6. in
Typeface Pica
Temperature
Celsius
C
1 K -273.15

Rankine
R
5.0/9.0 K

Fahrenheit
F
1 R -459.67

Mass
gram
g
0.001 kg
This is case sensitive.
gram
gm
g
(alternate symbol)
pound mass
lbm
0.45359237 kg
(avoirdupois)
Troy pound
lbt
0.3732417 kg
(apothecary)
carat (metric)
carat
0.2 g

slug
slug
1 lb sec^2/ft

snail
snail
1 lb sec^2/in

Short Ton
ton
2000 lbm

Long Ton
ton_l
2240 lbm

Ounce
oz
28.34952 g
(avoirdupois)
Grain
gr
64.79891 mg

Pennyweight
dwt
1.55174 g

Force or Weight
Newton
N
1 kg m/s^2

Dyne
dyn
1e-5 N

pound force
lb
lbm G

pound force
lbf
lbm G

poundal
poundal
1 lbm ft/sec^2

kilopound
kip
1000 lbf

kilogram force
kgf
kg G

Energy
Joule
J
1 N m

British Therm. Unit
BTU
1055.056 J
(International Table)
British Therm. Unit
Btu
1 BTU
alternate symbol
British Therm. Unit
BTU_th
1054.350 J
(Thermochemical)
calorie
cal
4.1868 J
(International Table)
calorie
cal_th
4.184 J
(Thermochemical)
Calorie
Cal
4.1868 kJ
(nutritionists)
electron volt
eV
1.602177e-19 J

erg
erg
1e-7 J

Ton of TNT
TNT
4.184e9 J

Power
Watt
W
1 J/s

Horse Power
hp
550 ft lb/s

Pressure
bar
bar
1e5 N/m^2

Pascal
Pa
1 N/m^2

Pounds per sq. inch
psi
1 lb/in^2

Pounds per sq. ft.
psf
1 lb/ft^2

kilo psi
ksi
1000.0 psi

atmospheres
atm
1.01325e5 N/m^2

inches of Mercury
inHg
3.387 kPa

millimeters Mercury
mmHg
0.1333 kPa

Torr
torr
1.333224 Pa

Volume or Area
Liter
L
1/1000.0 m^3

gallon
gal
3.785412 L

Pint (U.S. liquid)
pint
1/8. gal

Quart (U.S. liquid)
qt
2 pint

Pint (U.S. dry)
dpint
0.5506105 L

Quart (U.S. dry)
dqt
2 dpint

Acre
acre
1/640.0 smi^2

Hectare
ha
10000 m^2

Barrel (petroleum)
barrel
158.9873 L

Fluid Ounce
oz_fl
29.57353 mL

Gill (U.S.)
gi
0.1182941 L

Peck (U.S.)
pk
8.809768 L

Tablespoon
tbl
1/32. pint

Teaspoon
tsp
1/3. tbl

Cup
cup
16. tbl

Electromagnetism
Coulomb
Co
1 A s
Electric Charge
Volt
V
1 W/A
Electric Potential
Ohm
ohm
1 V/A
Electric Resistance
Ohm
\\Omega
1 V/A
alternate symbol
Faraday
faraday
96485.31 Co
Electric Charge
Farad
farad
Co/V
Capacitance
Stokes
stokes
1e-4 m^2/s

Oersted
Oe
79.57747 A/m

Webber
Wb
V s
Magnetic flux
Tesla
Tesla
Wb/m^2
Magnetic flux density
Henry
H
Wb/A
Inductance
Siemens
S
A/V
Electrical Conductance
Light and Radiation
Lux
lux
cd/m^2
Iluminance
Lux
lx
cd/m^2

Lumen
lm
cd
Luminous Flux
Stilb
sb
10000 cd/m^2

Phot
ph
10000 lx

Becquerel
Bq
s^-1
activity
Gray
Gy
J/kg
Absorbed Dose, kerma
Sievert
Sv
J/kg
Dose equivalent
Other Quantities
pound mole
lbmole
1 mol lbm/g
quantity
poise
poise
1 g /sec cm
viscosity
Gravity's accel.
G
9.80665 m/sec^2
Gravity on Earth
Degree
deg
Pi/180
Can be used to convert from degrees to radians for trig functions.
Percent
%
0.01

Knot
knot
1852 m/hr
velocity
Miles per Hour
mph
1 mi/hr
velocity
Gallon/minute
gpm
1. gal/min
flow rate
Revolution/minute
rpm
360 deg/min




Introduction:
You may need to convert Voltage, A mperage and electrical specifications from equipment into kW, kVA and BTU information that can be used to calculate overall power and HVAC requirements.  The following section addresses the process of taking basic electrical values and converting them into other types of electrical values.
The specification nameplates on most pieces of computer, radio or network equipment usually list required electrical power values.  These values are usually expressed in volts, amps, kilovolt-amps (kVA), Watts or some combination of all of the above.
If you are an architect or engineer using equipment nameplate information to compute power and cooling requirements, you will find that the total power and cooling values will exceed the actual run requirements of the equipment.  Reason:  the nameplate value is designed to ensure that the equipment will start and run safely.  Manufacturers build in a "safety factor" (sometimes called an "engineering cushion") when developing nameplate specifications.  Some nameplates specify  power requirements that are higher than the equipment will ever need.  The most common engineering solution is to utilize only 80% of available capacity and therefore your computed results will overstate the power and cooling equipment requirement by a factor close to 20%. 

Develop the power and cooling budget using the nameplate specifications inserted into the formulae below and use the resultant documentation as your baseline.  Document everything.  There will come a day when you will need every amp of power you projected.  Power budgets are notoriously consumed in a much shorter time than predicted.  Don't forget to add a "future factor" to your power and cooling budget.  Power supplies double in power draw and heat output every two to three years.  If you don't include these factors in your budgets, you will consume a 10 year power and cooling budget in three years (this happened to me, I know this is true).
Three Phase Power
You will notice that all of the equations that refer to three phase power contain the value 1.73 in the formula somewhere.  The value 1.73 is the square root of 3.  Intuitively, you can see how this value is applied in the formulae.  (3 phases therefore 1 phase = square root of 3)
Computing Watts When Volts and Amps are Known
        POWER (WATTS) = Volts x Amps
For example:
 a small computer has a nameplate that shows 2.5 amps.  Given a normal 120 Volt, 60 Hz power source and the ampere reading from equipment, make the following calculation:
        POWER (WATTS) = 2.5Amps x 120Volts = 300 WATTS
   Generally: P=IE  
P= Power(WATTS)
I = Current(Amps)
E = Voltage(Volts)
   So: I = P/E and E = P/I 
   Therefore: 1 Watt = 1 Ampere x 1 Volt
Computing Volt-Amps (VA)
       Same as above.  Volt-Amps (VA) = Volts x Amps    =  300 VA

Computing Kilovolt-Amps (kVA):
 kVA stands for "Thousand Volt-Amps".
A 2-Pole Single Phase 208-240 power source requires 2 hot wires from 2 different circuits (referred to as poles) from a power distribution panel.
       SINGLE PHASE
       KILOVOLT-Amps (kVA) = Volts x Amps / 1000
      
        Using the previous example:  120 x 2.5 = 300 VA       300 Va / 1000 = .3 kVA
       208-240 SINGLE-PHASE (2-POLE SINGLE-PHASE)

Example:  An enterprise computer bvserver with a 4.7 amp rating and requiring a 208-240 power source.  Use 220 volts for our calculations.
        kilovolt-Amps (kVA) = Volts x Amps /1000
   
        220 x 4.7 = 1034          1034 / 1000 = 1.034 kVA
       THREE-PHASE
Example:  A large disk storage system loaded with disks.  The equipment documentation shows a requirement for a 50-amp 208-240 VAC power source.  Do not calculate any value for the plug or receptacle.  Use 220 volts for the calculation.
        kilovolt-Amps (kVA) = Volts x Amps x 1.73 / 1000

        220 x 50 x 1.73 = 19,030       19,030 / 1000 =  19.030 kVA    This would be rounded to 19

Computing Kilo Watts:
Finding KiloWatts requires using a power factor in the computation.  The power factor is a number that adjusts the power calculation to reflect the efficiency of the use of the electricity supplied to the system.  This factor can vary widely (usually from 60% to 95%) and is never published on the equipment nameplate and is not often supplied with product information.  For purposes of these calculations, we use a power factor of .85.  This random number places a slight inaccuracy into the numbers.  Its OK and it gets us very close for the work we need to do.  Most UPS equipment will claim a power factor of 1.00.  It is common for the power factor to be considered 1.0 for devices less than 3 years old.
       SINGLE PHASE
Example: 
 We have a medium-sized Intel server that draws 6.0 amps and the power supply has a power factor of .85.
        kiloWatt (kW) = Volts x Amps x Power Factor / 1000
   
        120 x 6.0 = 720 VA       720 VA x .85 = 612      612 / 1000 = .612 kW
      208-240 SINGLE-PHASE (2-POLE SINGLE-PHASE)
Example:  An enterprise computer server has a 4.7 amp rating and requires a 208-240 power source.  I'll use 220 volts  and a power factor of .85 for our example calculations.
        kiloWatt (kW) = Volts x Amps x Power Factor x 2 / 1000
   
        220 x 4.7 x 2 = 2068          2068 x .85 = 1757.8      1757.8 / 1000 = 1.76 kW
       THREE-PHASE
Example: 
 A large storage system loaded with disks.  The equipment documentation shows a requirement for a 50-amp 208 VAC Power source.  Do not calculate any value for the plug or receptacle. Use 220 volts for the calculation.
        kiloWatt (kW) = Volts x Amps x Power Factor x 1.73
                                                     1000
        220 x 50 x .85 x 1.73  = 16,175.50    16,175.50/1000 = 16.175 kW

To Convert Between kW and kVA
The only difference between kW and kVA is the power factor.  The power factor, unless taken from the manufacturer's specifications, is an approximation.  For this example, we use a power factor of .95.  The kVA value will always be larger than the value for kW. 
        kW to kVA         kW / .95 =  kVA
        kVA TO kW       kVA x .95 =  kW

To Convert Between kW-Hours and kVA
There is NO conversion from kWH to kVA.  These are two different measures.  kWH is energy and kVA ispower (not necessarily dissipated).  If you look at kW (power) and kVA (power), then there is a relationship. That relationship is the power factor of the load.

Computing BTUs
Known Standard:   1 kW = 3413 BTUs (or 3.413 kBTUs)
If you divide the electrical nameplate BTU value by 3413 you may not get the published kW value.  If the BTU information is provided by the manufacturer, use it, otherwise use the above formula. 

Shotgun Section:
Here are conversions, short and sweet:
To convert kVA to Amps: 
Multiply kVA by 1000/voltage    [  (kVA x 1000) / E  ]
For 3 Phase power divide by 1.73    [ (kVA x 1000) / E x 1.73  ]  

To convert Watts to Volts when amps are known:
Voltage = Watts / Amps 
E = P / I 

To convert Watts to Amps when volts are known:
Amps = Watts / Voltage 
I = P / E 
For 3 Phase power divide  by 1.73

To convert Amps to Watts when volts are known:
Watts = Voltage x Amps 
P = E x I 
For 3 Phase power multiply  by 1.73

To convert Horsepower to Amps:
Horsepower = (E x I x EFF) / 746 
Efficiency = (746 x HP) / (V x A) 
Multiply Horsepower by 746W (1 HP = 746 Watts) 
Find Circuit Voltage and Phase 


   
HOW TO FIND KILOWATT-HOUR (KwH)
BTU * (2.9307 * 10 -4)
FtLb * (3.7661 * 10 -7)
Joule  * (2.7777 * 10 -7)
   
WHERE:
  E = VOLTS  
P = WATTS
  R = OHMS  
  I = AMPS  
  HP = HORSEPOWER  
  PF = POWER FACTOR  
  kW = KILOWATTS  
  kVA = KILOVOLT-AMPS  
  EFF = EFFICIENCY (decimal)  


Mechanical
General Approximations - RULES OF THUMB

Use these in the field for fast approximations:

At 3600 rpm, a motor develops a 1.5 lb-ft of torque per HP at rated HP output
At 1800 rpm, a motor develops a 3 lb-ft of torque per HP at rated HP output
At 1200 rpm, a motor develops a 4.5 lb-ft of torque per HP at rated HP output
At 900 rpm, a motor develops a 6 lb-ft of torque per HP at rated HP output

At 575 volts, a 3-phase motor draws 1 AMP per HP at rated HP output
At 460 volts, a 3-phase motor draws 1.25 AMP per HP at rated HP output
At 230 volts a 3-phase motor draws 2.5 AMP per HP at rated HP output

At 230 volts, a single-phase motor draws 5 AMP per HP at rated HP output
At 115 volts, a single-phase motor draws 10 AMP per HP at rated HP output

   

FORMULAS, EQUATIONS & LAWS

Symbolic:
E =VOLTS ~or~ (V = VOLTS)
P =WATTS ~or~ (W = WATTS)
R = OHMS ~or~ (R = RESISTANCE)
I =AMPERES ~or~ (A = AMPERES)
HP = HORSEPOWER
PF = POWER FACTOR
kW = KILOWATTS
kWh = KILOWATT HOUR
VA = VOLT-AMPERES
kVA = KILOVOLT-AMPERES
C = CAPACITANCE
EFF = EFFICIENCY (expressed as a decimal)








AddThis